Skip to main content
Siemens 3VA1180-3ED22-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-3ED22-0AA0 SENTRON MCCB, 80 A, 2-Pole, 75.6

MPN3VA1180-3ED22-0AA0
Active

Siemens SENTRON 3VA1180-3ED22-0AA0, molded case circuit breaker, 2-pole, 80 A, TM210 release, 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1180-3ED22-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1180-3ED22-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Power loss, max.12.8 W
3VA1180-3ED22-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1180-3ED22-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-3ED22-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1180-3ED22-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-3ED22-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

What this MCCB does and where it fits

It carries an 80 A continuous rating at 40 °C and holds that same 80 A all the way up to 50 °C; above that it derates gently to 74 A at 70 °C, so in a hot enclosure you still get most of the rated current. Breaking capacity is 75.6 kA at 240 V AC and 52.5 kA at 415 V AC, which covers high-fault utility feeds. It's IP40 on the front — fine for a dry indoor panel, not for washdown.

The 3VA1180-3ED22-0AA0 measures 130 mm high, 50.8 mm wide, and 70 mm deep — that's roughly 5.1 by 2 by 2.8 inches. Two-pole width at 50.8 mm is standard for a 2-pole MCCB in this class, so it drops into a DIN-rail or panel-mount assembly without re-drilling the gland plate. Insulation voltage is rated 500 V, so it's fine on 480 V systems with margin.

Frequently asked questions

Where can I buy 3VA1180-3ED22-0AA0 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability confirmation — no stock count or price is published here.

What is the breaking capacity of this MCCB?

At 240 V AC it's rated 75.6 kA; at 415 V AC it's 52.5 kA. That covers most commercial and light industrial high-fault service entrances.

What is the continuous current rating at elevated temperatures?

It's rated 80 A from 40 °C through 50 °C. At 55 °C it derates to 78 A, at 60 °C to 77 A, at 65 °C to 75 A, and at 70 °C to 74 A.

MPN
3VA1180-3ED22-0AA0