Skip to main content
Siemens 3VA1180-3EE32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-3EE32-0KH0 SENTRON MCCB, 80A, 75.6kA

MPN3VA1180-3EE32-0KH0

Siemens SENTRON 3VA1180-3EE32-0KH0, molded case circuit breaker, 3-pole, 80 A (40 °C), 75.6 kA breaking at 240 V, shunt trip release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1180-3EE32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11803EE320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1180-3EE32-0KH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.2 W
3VA1180-3EE32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1180-3EE32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-3EE32-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1180-3EE32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-3EE32-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1180-3EE32-0KH0 is a SENTRON molded case circuit breaker (MCCB) rated 80 A continuous at 40 °C, with a 75.6 kA interrupting capacity at 240 V — that's the number that tells you it'll clear a hard fault downstream without welding its contacts shut. It's a 3-pole unit built for line protection, meaning it guards the feeder, not a specific motor or load. That auxiliary stack gives you remote status — open/closed and tripped — without adding a separate module. The shunt trip lets you drop the breaker remotely via a control signal, which is handy for emergency-off circuits or PLC-driven load shedding.

Breaking capacity across voltages — the selectivity story

At 240 V it interrupts 75.6 kA; at 415 V that drops to 52.5 kA; at 440 V it's 32 kA; at 500 V and 690 V it holds at 11.9 kA. Those numbers govern your selectivity study — if your upstream transformer can push 65 kA at 480 V, this breaker at 32 kA (440 V) won't coordinate unless you step up to a higher-rated frame upstream. For a 240 V delta panel or a 400 V wye with moderate fault current, it's a solid fit.

Thermal derating and ambient reality

At 55 °C it's 78 A, at 60 °C it's 77 A, at 65 °C it's 75 A, and at 70 °C it's 74 A. The max power loss is 19.2 W, which matters for enclosure heat calc if you're stacking several breakers.

Frequently asked questions

What auxiliary switches come with this breaker?

It ships with 2 auxiliary switches plus 1 trip alarm switch HQ, giving you open/closed and tripped status without an add-on module.

MPN
3VA1180-3EE32-0KH0