Thermal derating — real-world current capacity
Above that, derating starts: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C (–).
Breaking capacity by system voltage
The interrupting rating drops as system voltage rises: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V (–).
Panel fit — dimensions and auxiliaries
The breaker measures 130 mm height, 76.2 mm width, and 70 mm depth — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mounted panel layouts. It ships with two factory-fitted HQ auxiliary switches for status feedback to the PLC or indication lamp.