Skip to main content
Siemens 3VA1180-3EF32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-3EF32-0AD0 SENTRON MCCB, 80 A, 3-Pole, 75.6

MPN3VA1180-3EF32-0AD0

Siemens SENTRON 3VA1180-3EF32-0AD0, molded case circuit breaker, 3-pole, 80 A rated current, TM240 thermal-magnetic release, 75.6 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1180-3EF32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1180-3EF32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1180-3EF32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1180-3EF32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-3EF32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1180-3EF32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-3EF32-0AD0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Its TM240 thermal-magnetic release provides fixed thermal and adjustable magnetic trip — the tr max is adjustable to 1 s for coordination studies. Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V, which covers most industrial panel fault-current requirements up to those levels.

At 55 °C it steps to 76.8 A, and at 70 °C it's still 72 A, so a warm panel near a curing press or furnace line doesn't force an upsized frame. The 3-pole design with three auxiliary switches (HQ type) gives status feedback for PLC or light-tower indication without an add-on module. Front IP40 protection handles dry indoor panels; not rated for washdown.

Frequently asked questions

Does 3VA1180-3EF32-0AD0 include auxiliary contacts?

Yes, it ships with three auxiliary switches (HQ type) for status feedback.

MPN
3VA1180-3EF32-0AD0