Skip to main content
Siemens 3VA1180-3EF32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1180-3EF32-0CC0 MCCB, 80 A, 3-pole, TM240

MPN3VA1180-3EF32-0CC0

Siemens SENTRON 3VA series, Molded case circuit breaker, 3VA1180-3EF32-0CC0, 80 A, 3-pole, TM240 thermal-magnetic release, 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1180-3EF32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1180-3EF32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1180-3EF32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1180-3EF32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-3EF32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1180-3EF32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-3EF32-0CC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Line protection MCCB with TM240 release

Breaking capacity is rated at 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. Current rating holds at 80 A from 40 °C through 50 °C ambient, then derates to 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C. In a sealed panel running at 55 °C, you lose 3.2 A of headroom — plan the load accordingly.

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that mounts on a DIN rail or panel plate. The integrated auxiliary trip is order code 3VA9608-0BB24 — a separate line item if you need a shunt trip or additional signaling.

Frequently asked questions

How do I get current pricing and availability for 3VA1180-3EF32-0CC0?

Submit an RFQ through this listing. The part is sourced through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings for 3VA1180-3EF32-0CC0?

Rated continuous current Iu is 80 A, insulation voltage Ui is 800 V, breaking capacity is 75.6 kA at 240 V and 52.5 kA at 415 V. It uses a TM240 thermal-magnetic overcurrent release.

What is the depth of 3VA1180-3EF32-0CC0?

Depth is 70 mm. Overall dimensions are 130 mm height, 76.2 mm width, 70 mm depth.

MPN
3VA1180-3EF32-0CC0