Thermal derating and panel fit
The 3VA1180-3EF32-0HH0: The 80 A rating holds flat through 50 °C ambient; above that it derates to 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C. Operating ambient range is -25 °C to 70 °C, storage from -40 °C to 80 °C. Physical footprint is 130 mm high, 76.2 mm wide, 70 mm deep — fits standard panel-mount cutouts for 3-pole MCCBs in the 80 A class. Front protection is IP40, suitable for enclosed distribution boards.
Integrated auxiliary and shunt trip
Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration) and a shunt trip release (STL) for remote tripping. The shunt trip order code is 3VA9688-0BL30. No undervoltage release, no ground-fault monitoring, no communication function, no phase-failure detection — this is a straightforward line-protection breaker with basic remote-trip capability.