Siemens 3VA1180-3EF36-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-3EF36-0AF0 SENTRON MCCB, 80A, 3-Pole, TM240

MPN3VA1180-3EF36-0AF0

Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1180-3EF36-0AF0, 3-pole, 80 A (40 °C), TM240 thermal-magnetic release, 70 mm depth, line protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-3EF36-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11803EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1180-3EF36-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-3EF36-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1180-3EF36-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-3EF36-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1180-3EF36-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-3EF36-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1180-3EF36-0AF0 — 80 A SENTRON MCCB for Line Protection

The Siemens 3VA1180-3EF36-0AF0 is a 3-pole SENTRON molded case circuit breaker (MCCB) designed for line protection, carrying a continuous current rating of 80 A at 40 °C and holding that rating through 50 °C before a gentle derating curve begins — 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. That thermal stability means this breaker fits enclosures with limited airflow without forcing a downsized selection at typical panel ambient temperatures. Breaking capacity spans the voltage range: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. The TM240 thermal-magnetic release provides fixed instantaneous and overload protection — no electronic adjustment, which simplifies specification for standard distribution panels where the fault current profile is well understood. Rated insulation voltage is 800 V, and the auxiliary switch configuration comes as 1 auxiliary switch + 1 trip alarm switch HQ — useful for remote status indication without adding a separate accessory module.

Panel Fit and Mounting

Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth — a compact footprint for a 3-pole MCCB in this current class. The 70 mm depth is the key number for gland-plate clearance and DIN-rail enclosure depth; it fits standard 200 mm deep enclosures with room for wiring gutters.

Frequently asked questions

Where can I buy 3VA1180-3EF36-0AF0 and get a price?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

What is the depth of 3VA1180-3EF36-0AF0?

The depth is 70 mm (2.76 in), which is the dimension that determines clearance behind the panel door or gland plate.

What is the width of 3VA1180-3EF36-0AF0?

The width is 76.2 mm (3 in), which sets the DIN-rail or mounting-plate spacing for multi-breaker layouts.

What breaking capacity does this MCCB have at 415 V?

At 415 V the breaking capacity is 52.5 kA — sufficient for most industrial distribution boards with typical transformer sizes up to 1500 kVA.

MPN