The thermal derating curve holds flat at 80 A through 50 °C, then steps down to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C — useful to check if your panel ambient runs warm. Breaking capacity varies sharply with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
The 3-pole footprint matches standard MCCB mounting in distribution boards and motor control centers.