Specifications

Identification

3VA1180-4EF32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11804EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1180-4EF32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.21.7 W

Protection & Trip Unit

3VA1180-4EF32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1180-4EF32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-4EF32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1180-4EF32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-4EF32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1180-4EF32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection. It carries 80 A continuously at 40 °C ambient, with a maximum breaking capacity of 121 kA at 240 V — enough to handle high-fault utility feeds or large transformer secondaries without cascading upstream. The 121 kA interrupting rating at 240 V means this breaker can safely clear a bolted fault at that level, preserving selectivity downstream. At 415 V it still breaks 75.6 kA, and at 690 V it holds 11.9 kA — the SCCR curve drops with voltage, so verify the available fault current at your system voltage. Rated insulation voltage is 800 V, and the unit includes an undervoltage release (UVR) plus two factory-fitted auxiliary switches (HQ design) for status feedback to a PLC or annunciator panel.

Thermal derating and panel fit

The breaker holds its full 80 A rating up to 50 °C ambient. Above that it derates linearly to 74 A at 70 °C — a useful margin for a sealed, non-ventilated enclosure. Maximum power loss is 21.7 W, so account for that heat when sizing the cabinet's thermal budget. Dimensions are 70 mm deep, 76.2 mm wide, and 130 mm tall — a standard 3-pole MCCB footprint that drops into most SENTRON panelboards and distribution blocks without re-drilling the mounting plate.

Frequently asked questions

Where can I buy 3VA1180-4EF32-0CC0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation.

What is the breaking capacity of this MCCB at 240 V?

The maximum breaking capacity at 240 V is 121 kA. At 415 V it is 75.6 kA, at 440 V it is 52.5 kA, and at 500 V and 690 V it is 11.9 kA.

MPN