Specifications

3VA1180-4EF36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1180-4EF36-0DH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1180-4EF36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1180-4EF36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-4EF36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1180-4EF36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-4EF36-0DH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1180-4EF36-0DH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 80 A continuous at up to 50 °C ambient without derating — above that it steps down to 76.8 A at 55 °C and 72 A at 70 °C, so the thermal curve is flat across most panel environments. Breaking capacity hits 121 kA at 240 V, 75.6 kA at 415 V, and 52.5 kA at 440 V — numbers that cover most industrial distribution boards and motor control centers fed from a transformer of moderate impedance.

The 3VA1180-4EF36-0DH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a compact footprint for a 3-pole MCCB at this interrupting level, so it fits standard distribution panelboards without crowding adjacent breakers.

The integrated auxiliary trip uses order code 3VA9608-0BB25 — order that separately if you need a spare release module.

Frequently asked questions

Does this breaker include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as standard, which trips the breaker when supply voltage drops below a set threshold.

What auxiliary contacts come with this MCCB?

It includes 2 auxiliary switches plus 1 trip alarm switch (HQ type), providing status feedback for remote monitoring or PLC inputs.

MPN