Skip to main content
Siemens 3VA1180-4GF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-4GF42-0AA0 SENTRON 4-Pole MCCB, 80 A, 121 kA

MPN3VA1180-4GF42-0AA0
Active

Siemens SENTRON 3VA1180-4GF42-0AA0, 4-pole molded case circuit breaker, 80 A rated current, TM240 thermal-magnetic release, 121 kA interrupting at 240 V, 75.6 kA at 415 V, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-4GF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1180-4GF42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-4GF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1180-4GF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-4GF42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1180-4GF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-4GF42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

80 A, 4-pole MCCB with 121 kA interrupting capacity

The Siemens SENTRON 3VA1180-4GF42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 80 A continuous current at 40 °C, with a TM240 thermal-magnetic release. Its interrupting capacity reaches 121 kA at 240 V and 75.6 kA at 415 V, which means it can safely clear high-fault currents in low-voltage distribution without upstream damage. The 800 V rated insulation voltage (Ui) supports use in 480/277 V and 600 V systems with adequate margin. The 70 mm depth and 101.6 mm width fit standard panel-mount cutouts for 4-pole MCCBs. Front protection is IP40, so it tolerates tool contact but not water ingress — install inside a rated enclosure for wet environments.

Thermal derating and DC capability

The 80 A rating holds steady up to 50 °C ambient. Above that, derating is gradual: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. If the panel runs hot, the effective continuous current drops by about 7.5% at the top of the operating range. Maximum power loss is 19.2 W per pole — factor that into enclosure thermal calculations. For DC circuits, the maximum rated operational voltage is 600 V DC. The interrupting ratings at 500 V and 690 V AC are both 11.9 kA, so the breaker handles standard 400 V-class motor branch circuits with typical fault levels.

Panel integration notes

The 4-pole design with 100% N-conductor protection means the neutral pole is fully rated and switches with the phases — no derating needed for the neutral path. The TM240 release is thermal-magnetic: the thermal element handles overloads up to the trip curve, and the magnetic element responds to short-circuit currents. No communication function is built in; if remote monitoring is required, the optional motor drive (Product Extension / Optional / Motor Drive: Yes) allows remote open/close via a separate actuator. Storage temperature range is -40 °C to 80 °C; operating range is -25 °C to 70 °C. The storage minimum is the binding limit for cold warehouse conditions — the breaker can sit in unheated storage without damage.

Frequently asked questions

How do I get current pricing and availability for 3VA1180-4GF42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead-time estimate.

What is the interrupting capacity of 3VA1180-4GF42-0AA0 at 415 V?

At 415 V, the interrupting capacity is 75.6 kA. This is the maximum fault current the breaker can safely interrupt at that voltage level.

What compliance documentation does this brand provide for 3VA1180-4GF42-0AA0?

As a Siemens SENTRON product, this MCCB is designed to meet IEC 60947-2 and relevant UL/CSA standards. The manufacturer provides RoHS and REACH declarations, along with the device manual for DC application details referenced in the spec.

MPN
3VA1180-4GF42-0AA0