Skip to main content
Siemens 3VA1180-5EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-5EE32-0AA0 SENTRON MCCB, 80 A, 3-Pole, 187 k

MPN3VA1180-5EE32-0AA0
Active

Siemens SENTRON 3VA1180-5EE32-0AA0, 3-pole molded case circuit breaker, 80 A (40 °C), TM220 release, 187 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-5EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1180-5EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-5EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1180-5EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-5EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1180-5EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-5EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1180-5EE32-0AA0 – 80 A MCCB for Line Protection

The Siemens SENTRON 3VA1180-5EE32-0AA0 is a 3-pole molded case circuit breaker rated 80 A at 40 °C with a TM220 thermal-magnetic overcurrent release, designed for line protection in distribution panels. Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, and 75.6 kA at 440 V — figures that place it in the high-fault category for industrial switchgear, suitable for installations with high available fault current. The TM220 release combines a thermal element for overload protection and a magnetic element for short-circuit protection, with no undervoltage release or ground-fault monitoring fitted as standard.

Integration & Mounting

The 3VA1180-5EE32-0AA0 measures 70 mm deep, 76.2 mm wide, and 130 mm high, fitting standard panel cutouts for 3-pole MCCBs in the 80 A frame class. IP40 protection on the front allows installation in enclosed distribution boards where no water ingress is expected; the open back requires the panel enclosure to provide the overall IP rating. Maximum power loss at rated current is 19.2 W — factor this into thermal calculations for enclosed panels, especially when multiple breakers are ganged.

Ratings & Derating

Current rating holds at 80 A from 40 °C through 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C — the thermal curve governs actual continuous capacity in warm cabinets. Rated insulation voltage is 800 V, and operating temperature range spans -25 °C to +70 °C, with storage from -40 °C to +80 °C.

Frequently asked questions

What is the depth of 3VA1180-5EE32-0AA0?

The depth is 70 mm (2.76 in).

MPN
3VA1180-5EE32-0AA0