The built-in shunt trip (STL) release lets a remote signal or safety relay trip the breaker independently of overcurrent — useful for emergency-stop circuits or fire-suppression interlocks. Two auxiliary switches (HQ) report contact position back to a PLC or status panel.
Derating and thermal limits
Above that, it derates gradually: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C.
The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole footprint that fits standard Siemens 3VA mounting bases. No undervoltage release is fitted, so if your safety circuit expects one, you'll add it externally or order a variant with that option.