Above that, it derates: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C.
Integrated accessories and release options
It does not include an undervoltage release or ground-fault monitoring. The basic switch supplied is 3VA11805EF360AA0. Communication function is not fitted — this is a standalone line-protection breaker, not a metering or networked unit.
Footprint is 76.2 mm wide (3 in), 130 mm tall (5.12 in), 70 mm deep (2.76 in). Three-pole construction. Mounts into a standard SENTRON panelboard or distribution enclosure; the 70 mm depth leaves clearance for rear-connected busbars in most shallow enclosures. Trip indicator and voltage trigger are present.