Siemens 3VA1180-5GD46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-5GD46-0AA0 SENTRON MCCB, 80A 4-Pole, 187kA a

MPN3VA1180-5GD46-0AA0
Active

Siemens SENTRON 3VA1180-5GD46-0AA0, 4-pole molded case circuit breaker, 80 A rated current (Iu), TM210 thermal-magnetic release, line protection version, 187 kA breaking capacity at 240 V, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-5GD46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1180-5GD46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-5GD46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1180-5GD46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-5GD46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1180-5GD46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-5GD46-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

80 A MCCB with 187 kA interrupting capacity — selectivity headroom for distribution panels

The Siemens SENTRON 3VA1180-5GD46-0AA0 is a 4-pole molded case circuit breaker rated 80 A continuous current (Iu) at 40 °C, with a TM210 thermal-magnetic release. Its interrupting capacity hits 187 kA at 240 V AC, 121 kA at 415 V, and 75.6 kA at 440 V — enough headroom to coordinate selectively with downstream branch breakers in high-fault industrial distribution. Rated insulation voltage Ui is 800 V, and the breaker carries a full thermal derating curve from 80 A at 40 °C down to 74 A at 70 °C. Power loss maxes at 19.2 W. Front protection is IP40 — suitable for enclosed panel mounting, not washdown environments.

Sourcing and lifecycle — active line, quoted to order

No official successor or replacement has been issued; the 3VA1 platform remains the current SENTRON molded-case offering. For BOM-freeze planning, the part carries standard Siemens compliance documentation (RoHS, REACH, UL, IEC) available on request.

Panel fit and integration

Dimensions are 101.6 mm wide, 130 mm tall, 70 mm deep — a 4-pole MCCB that fits standard distribution panel mounting. The TM210 release is fixed thermal-magnetic (no electronic trip unit), so no auxiliary power or programming is needed. No undervoltage release, no ground-fault monitoring, no communication module on this variant — it is a straight line-protection breaker. N-conductor protection is rated at 100 % (full-rated neutral). Storage temperature range is -40 to 80 °C; operating range is -25 to 70 °C. The IP40 front rating means the breaker face is protected against solid objects over 1 mm but not sealed against moisture — keep it inside the enclosure.

Frequently asked questions

What is the breaking capacity of 3VA1180-5GD46-0AA0 at different voltages?

187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. These are the rated ultimate short-circuit breaking capacities (Icu) for this 4-pole 80 A MCCB.

Where can I buy 3VA1180-5GD46-0AA0 and how is it quoted?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What type of release does 3VA1180-5GD46-0AA0 use?

It uses a TM210 thermal-magnetic overcurrent release — fixed thermal and magnetic trip settings, no electronic adjustment. This is a line-protection version (not for motor or generator protection).

MPN
3VA1180-5GD46-0AA0