Skip to main content
Siemens 3VA1180-5GF46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-5GF46-0AA0 SENTRON MCCB, 80 A, 4-Pole, 187 k

MPN3VA1180-5GF46-0AA0
Active

Siemens SENTRON 3VA1180-5GF46-0AA0, molded case circuit breaker, 4-pole, 80 A, TM240 thermal-magnetic release, 187 kA interrupting capacity at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-5GF46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1180-5GF46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-5GF46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1180-5GF46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-5GF46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1180-5GF46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-5GF46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

80 A, 4-pole MCCB with TM240 release — line protection for high-fault panels

The Siemens SENTRON 3VA1180-5GF46-0AA0 is a 4-pole molded case circuit breaker rated 80 A continuous, designed for line protection in distribution panels. Its TM240 thermal-magnetic release provides fixed overload and short-circuit curves — no trip indicator, no undervoltage release, no communication function. This is a straight line-protection breaker: feed it, protect the bus, move on. Interrupting capacity is the headline here: 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and still 17 kA at 690 V. That 187 kA figure at 240 V means it handles high-fault scenarios common on large transformer secondaries or industrial service entrances — not a standard branch breaker. The 4-pole configuration covers three-phase-plus-neutral or dual-supply switching where full isolation is required. Thermal derating is minimal up to 50 °C — still 80 A — then drops to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. That flat curve through 50 °C means it holds full rating in most ventilated enclosures; only tight, hot cabinets force a derate. Max power loss is 19.2 W, so heat dissipation inside the panel is manageable.

Panel fit — footprint and mounting

The 3VA1180-5GF46-0AA0 measures 70 mm deep, 101.6 mm wide, 130 mm tall. That 101.6 mm width (4 inches) is the standard 4-pole MCCB footprint — it occupies four 25 mm module spaces on a DIN rail or mounts directly to a backplate via the screw terminals. IP40 on the front means it's protected against tools and wires >1 mm, but not against water ingress; keep it inside the enclosure.

Frequently asked questions

Where can I buy 3VA1180-5GF46-0AA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing; no stock count or price is listed here.

What is 3VA1180-5GF46-0AA0's interrupting capacity at 240 V?

It interrupts 187 kA at 240 V AC, which covers high-fault scenarios on large transformer secondaries or industrial service entrances.

What is the thermal derating curve for this breaker?

Full 80 A through 50 °C, then 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. The flat curve through 50 °C means it holds rating in most ventilated enclosures.

MPN
3VA1180-5GF46-0AA0