Siemens 3VA1180-6EE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-6EE42-0AA0 SENTRON MCCB, 80A, 220kA at 240V

MPN3VA1180-6EE42-0AA0
Active

Siemens SENTRON 3VA1180-6EE42-0AA0, 4-pole molded case circuit breaker, 80 A rated at 40 °C, 220 kA breaking capacity at 240 V, TM220 thermal-magnetic release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-6EE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1180-6EE42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-6EE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1180-6EE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-6EE42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1180-6EE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-6EE42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The Siemens 3VA1180-6EE42-0AA0 is a SENTRON 4-pole molded case circuit breaker rated 80 A continuous at 40 °C, with a TM220 thermal-magnetic overcurrent release designed for line protection. Breaking capacity reaches 220 kA at 240 V, dropping to 154 kA at 415 V and 121 kA at 440 V — figures that cover high-fault industrial services where upstream transformer capacity is large. The 70 mm depth and 101.6 mm width match the standard SENTRON 3VA footprint for panel integration.

Breaking capacity and thermal derating

At 500 V and 690 V the interrupting rating is 17 kA — still adequate for most 480/600 V distribution, but not for high-fault 690 V services. The thermal derating curve holds 80 A flat through 50 °C, then steps down: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. That 6 A drop from 50 °C to 70 °C is tight — the breaker runs near its full rating even in a warm enclosure. Insulation voltage is rated 800 V, so the 690 V application is within the dielectric margin.

Panel integration notes

Mounts on a DIN rail or directly to a backplate via the 4-pole base. Front IP40 protects against tool entry and solid objects larger than 1 mm — adequate for clean indoor panels, not for washdown zones. No undervoltage release, no shunt trip, no communication module on this variant; the TM220 release is purely thermal-magnetic, so trip indication is mechanical (handle position). Power loss at full load is 19.2 W — factor that into enclosure thermal calculations.

Frequently asked questions

Where can I buy 3VA1180-6EE42-0AA0?

Sourced to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of 3VA1180-6EE42-0AA0 at 240 V?

220 kA at 240 V, dropping to 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V.

MPN