Skip to main content
Siemens 3VA1180-6EF32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-6EF32-0CH0 SENTRON MCCB, 80 A, 3-Pole, 220 k

MPN3VA1180-6EF32-0CH0

Siemens SENTRON 3VA1180-6EF32-0CH0, molded case circuit breaker, 3-pole, 80 A, TM240 release, line protection, 220 kA at 240 V, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1180-6EF32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1180-6EF32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA
3VA1180-6EF32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1180-6EF32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-6EF32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1180-6EF32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-6EF32-0CH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The TM240 thermal-magnetic release means the thermal element tracks load heating; the magnetic trip is fixed at 240 A nominal, so it clears bolted faults fast without nuisance trips on motor inrush.

Interrupting rating drops with system voltage: 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. If your panel feeds a 690 V drive bus, that 17 kA figure governs the SCCR — verify it against the available fault current upstream.

Thermal derating and ambient

Above that, it begins to taper: 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C.

Auxiliaries and releases

This variant includes an undervoltage release (UVR) — the auxiliary release design is listed as undervoltage release. The trip indicator is present, so you get a local mechanical flag when the breaker trips on fault.

Physical fit

The breaker measures 70 mm deep, 76.2 mm wide, 130 mm tall — a 3-pole frame that fits standard SENTRON panel footprints.

Frequently asked questions

How do I get current pricing and availability for 3VA1180-6EF32-0CH0?

Submit an RFQ through this listing. The part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is 3VA1180-6EF32-0CH0's interrupting capacity at 240 V?

220 kA at 240 V. It also carries 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V.

Will 3VA1180-6EF32-0CH0 drop into a panel specified around 3VA1112-5EF32-0CA0 without rewiring?

Both are 3-pole SENTRON MCCBs in the same frame family, so the mounting footprint and bus-bar spacing are identical. The auxiliary contact configuration and release type differ — verify the undervoltage release wiring and the auxiliary switch count match your control circuit before swapping.

MPN