Skip to main content
Siemens 3VA1180-6EF32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-6EF32-0JC0 SENTRON MCCB, 80A, 220kA at 240V

MPN3VA1180-6EF32-0JC0

Siemens SENTRON 3VA1180-6EF32-0JC0, molded case circuit breaker, 3-pole, 80 A at 40 °C, 220 kA interrupting at 240 V, line protection, with shunt trip (STL) and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-6EF32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11806EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1180-6EF32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-6EF32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1180-6EF32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-6EF32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1180-6EF32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-6EF32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

80 A MCCB with 220 kA interrupting capacity at 240 V

The Siemens SENTRON 3VA1180-6EF32-0JC0 is a 3-pole molded case circuit breaker rated 80 A at 40 °C, with a short-circuit breaking capacity of 220 kA at 240 VAC — enough to handle high-fault utility feeds or transformer secondaries without cascading upstream. At 415 V it still interrupts 154 kA, and at 690 V it holds 17 kA, covering most industrial distribution voltages. The 800 V rated insulation voltage means it's suitable for 480/277 V and 600 V panels with margin. Rated current holds at 80 A from 40 °C through 50 °C ambient, then derates gradually to 74 A at 70 °C (-). If your panel runs hot near the top of a cabinet, the 70 °C figure is the one to budget against. The unit draws 19.2 W maximum power loss at rated load — factor that into enclosure thermal calculations. This variant is configured for line protection and includes a shunt trip release (STL) plus two HQ auxiliary switches. The shunt trip allows remote tripping via a control signal — useful for emergency-stop circuits or interlocking with upstream gear. No undervoltage release, no ground-fault monitoring, no communication module.

Panel fit and mounting

At 76.2 mm wide, 130 mm tall, and 70 mm deep (-), the 3VA1180-6EF32-0JC0 fits the standard SENTRON 3VA frame footprint. It mounts directly to a DIN rail or panel-mount baseplate — no adapter needed. The 70 mm depth is shallow enough for most 200 mm deep enclosures, leaving room for wiring behind the breaker.

Frequently asked questions

What is the interrupting capacity of 3VA1180-6EF32-0JC0 at different voltages?

At 240 V it interrupts 220 kA, at 415 V it interrupts 154 kA, at 440 V it interrupts 121 kA, and at 500 V and 690 V it interrupts 17 kA (-). These ratings cover everything from high-fault utility feeds to standard industrial distribution.

What accessories are included with this MCCB?

This variant includes a shunt trip release (STL) for remote tripping and two HQ auxiliary switches for status signaling. It does not include an undervoltage release, ground-fault monitoring, or communication module.

Where can I buy 3VA1180-6EF32-0JC0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA1180-6EF32-0JC0