The 3-pole construction suits three-phase loads like motor feeders, lighting distribution, or sub-panel mains. An integrated auxiliary switch and trip alarm switch (1 AUX + 1 HP) give remote status indication — useful for PLC-based monitoring or alarm annunciation in automated lines.
Breaking capacity across voltage levels
Breaking capacity drops with system voltage: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V.
Rated current holds at 80 A from 40 °C through 50 °C, then derates linearly to 74 A at 70 °C.