Skip to main content
Siemens 3VA1180-6EF36-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-6EF36-0HH0 SENTRON MCCB, 80 A, 220 kA at 240

MPN3VA1180-6EF36-0HH0

Siemens SENTRON 3VA1180-6EF36-0HH0, 3-pole molded case circuit breaker, 80 A rated continuous current (Iu), TM240 thermal-magnetic release, 220 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1180-6EF36-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1180-6EF36-0HH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA
3VA1180-6EF36-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1180-6EF36-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-6EF36-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1180-6EF36-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-6EF36-0HH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity and coordination headroom

Its interrupting capacity hits 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and still holds 17 kA at 690 V — which means this breaker is built for high-fault locations like transformer secondaries or large busway feeds where the available fault current is serious. The TM240 thermal-magnetic release handles the overload and short-circuit protection; no ground-fault monitoring or communication module on this variant.

Thermal derating — what it actually means for the panel

At 55 °C it derates to 76.8 A, then 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C.

Auxiliaries and trip options

The integrated auxiliary trip order code is 3VA9688-0BL30. A voltage trigger and mechanical trip indicator are present; undervoltage release and phase-failure detection are not fitted on this variant.

Frequently asked questions

Where can I buy 3VA1180-6EF36-0HH0 and get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — figures are confirmed at quote time.

What is the closest functional second-source to 3VA1180-6EF36-0HH0?

The 3VA1110-5EE32-0JA0 is a peer in the same SENTRON 3VA family, but it is a different frame size and release variant. Verify the interrupting capacity and footprint before substituting — the 3VA1180 carries higher SCCR at 240 V (220 kA) and a TM240 release, while the 3VA1110 uses a different thermal-magnetic curve and lower frame rating.

Will 3VA1180-6EF36-0HH0 drop into a panel wired for 3VA1110-5EE32-0JA0?

Not without checking the mounting footprint and lug spacing. The 3VA1180 is a larger frame than the 3VA1110 — dimensions differ. Rewiring or a different backplate cutout may be required.

What compliance documentation is available for 3VA1180-6EF36-0HH0?

As a Siemens SENTRON MCCB, it carries the usual CE, UL, and CSA certifications for the series. Specific declaration files (RoHS, REACH) are available from Siemens upon request.

MPN