Skip to main content
Siemens 3VA1180-6GD46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-6GD46-0AA0 SENTRON MCCB, 80 A, 4-Pole, 220 k

MPN3VA1180-6GD46-0AA0
Active

Siemens SENTRON 3VA1180-6GD46-0AA0, molded case circuit breaker, 4-pole, 80 A, TM210 overcurrent release, line protection, 220 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1180-6GD46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1180-6GD46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.2 W
3VA1180-6GD46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1180-6GD46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1180-6GD46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1180-6GD46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1180-6GD46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

80 A MCCB with 220 kA interrupting capacity — line protection for high-fault panels

The Siemens SENTRON 3VA1180-6GD46-0AA0 is a 4-pole molded case circuit breaker rated 80 A continuous, designed for line protection in distribution panels where fault currents can reach 220 kA at 240 V. That interrupting rating drops to 154 kA at 415 V and 121 kA at 440 V, then to 17 kA at 500 V and 690 V — so the voltage class of your service entrance or sub-feed determines whether this breaker has headroom or is at its limit.

Above that it derates: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C.

Four-pole width at roughly 102 mm means it occupies two standard 54 mm DIN modules plus a sliver — verify the backpanel layout if replacing a narrower 3-pole unit. No undervoltage release or communication module is fitted on this variant; the TM210 release is self-powered.

Frequently asked questions

How do I get current pricing and availability for 3VA1180-6GD46-0AA0?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; pricing and stock levels are confirmed at quote time.

What is the breaking capacity of this MCCB at different voltages?

Rated interrupting capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. The steep drop above 440 V means this breaker is best suited for low-voltage high-fault applications, not 690 V distribution.

What type of overcurrent release does this breaker use?

It uses a TM210 thermal-magnetic release — no external trip unit, no communication, no ground-fault monitoring. Designed for straightforward line protection without auxiliary electronics.

MPN
3VA1180-6GD46-0AA0