Skip to main content
Siemens 3VA1180-6GF46-0KF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1180-6GF46-0KF0 SENTRON MCCB, 80 A, 4-Pole, 220 k

MPN3VA1180-6GF46-0KF0

Siemens SENTRON 3VA1180-6GF46-0KF0, molded case circuit breaker, 4-pole, 80 A, breaking capacity 220 kA at 240 V, with shunt trip (STL) and auxiliary switch + trip alarm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1180-6GF46-0KF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11806GF460AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1180-6GF46-0KF0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1180-6GF46-0KF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1180-6GF46-0KF0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1180-6GF46-0KF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1180-6GF46-0KF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1180-6GF46-0KF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

80 A, 4-pole MCCB with shunt trip — SENTRON 3VA series

The Siemens SENTRON 3VA1180-6GF46-0KF0 is a 4-pole molded case circuit breaker rated for 80 A continuous, designed for line protection in distribution panels. Its breaking capacity reaches 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — figures that drop to 17 kA at both 500 V and 690 V, so the voltage class of your fault bus determines whether this breaker clears without cascading upstream. The 80 A rating holds steady from 40 °C through 50 °C; above that it derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. If your panel ambient runs above 50 °C, the continuous load must stay under the derated value — the breaker will not trip earlier, but the internal bimetal follows the curve.

Built-in shunt trip and auxiliary switching

This variant ships with a shunt trip release (STL) for remote tripping and a 1 auxiliary switch + 1 trip alarm switch HQ combination. The shunt trip lets a safety PLC or remote E-stop signal open the breaker without an operator at the panel — useful for emergency-off circuits or remote load shedding. The auxiliary switch reports the breaker's open/closed state back to the control system; the trip alarm switch signals when it has opened on fault, not by manual command.

Mounting and integration

Dimensions are 130 mm height, 101.6 mm width, 70 mm depth — a standard SENTRON 3VA footprint that mounts on DIN rail or panel-mount base. The 4-pole width (101.6 mm) occupies the same slot width as other 4-pole 3VA breakers; if you are swapping from a different brand's 4-pole MCCB, check the busbar pitch and terminal spacing against the existing panel layout.

Frequently asked questions

Where can I buy 3VA1180-6GF46-0KF0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing at quote time.

What is 3VA1180-6GF46-0KF0's breaking capacity at different voltages?

Breaking capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. The voltage class of your fault bus determines the available fault current the breaker must interrupt.

Does this MCCB include a shunt trip or undervoltage release?

It includes a shunt trip release (STL) for remote tripping, but no undervoltage release. The auxiliary switch complement is one auxiliary switch plus one trip alarm switch HQ.

MPN
3VA1180-6GF46-0KF0