Siemens SENTRON 3VA1196-3ED16-0AA0, 1-pole molded case circuit breaker, 16 A rated current, 52.5 kA breaking capacity at 240 V AC, TM210 thermal-magnetic release, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1196-3ED16-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1196-3ED16-0AA0 — Ratings
ParameterValue
Number of poles1
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classN
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V7.5 kA
Power loss, max.3.53 W
3VA1196-3ED16-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1196-3ED16-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1196-3ED16-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1196-3ED16-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1196-3ED16-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.12 in
Width (in)1 in
Depth (in)2.76 in

Product details

What this 1-pole MCCB does on the line

The Siemens 3VA1196-3ED16-0AA0 is a 1-pole SENTRON molded case circuit breaker sized for 16 A continuous at 40 °C ambient, with the TM210 thermal-magnetic release tuned for line protection — no undervoltage release, no ground-fault monitoring, no communication module. At 240 V AC it interrupts faults up to 52.5 kA; at 415 V AC the breaking capacity drops to 7.5 kA, which is the number to watch if your panel feeds a 400 V bus. The 25.4 mm width (one inch) and 70 mm depth let it slot into a standard DIN-rail enclosure without crowding adjacent poles.

Rated current holds flat at 16 A from 40 °C through 55 °C; at 60 °C it derates to 15 A, and at 70 °C it stays at 15 A. That means no thermal headroom penalty in a warm panel unless you push past 55 °C — useful for a tightly packed row of breakers. The 52.5 kA interrupting rating at 240 V AC is the headline number, but the 7.5 kA at 415 V AC is the one that governs a 400 V three-phase distribution board; if your available fault current at the panel exceeds 7.5 kA at 415 V, this breaker needs an upstream current-limiting device. Power loss is 3.53 W max — negligible for heat budgeting in a multi-pole assembly.

Mounts on DIN rail via the integral clip. Front IP40 is standard for a distribution board — no gasket needed for dry indoor enclosures. The 70 mm depth leaves clearance behind a typical 100 mm deep gland plate; no right-angle cable bend issues. No auxiliary contacts or shunt trip are built in (no undervoltage release, no trip indicator), so if the BOM calls for remote signaling, you need the separate 3VA accessories kit.

Frequently asked questions

Where can I buy 3VA1196-3ED16-0AA0 and how is it quoted?

It is sourced through independent distribution and quoted to order against an RFQ; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 240 V and 415 V?

At 240 V AC the interrupting rating is 52.5 kA; at 415 V AC it is 7.5 kA.

What is the rated current and thermal derating for 3VA1196-3ED16-0AA0?

Rated 16 A continuous from 40 °C to 55 °C; derates to 15 A from 60 °C to 70 °C.

What compliance documentation does Siemens provide for this breaker?

The SENTRON 3VA series carries IEC/EN 60947-2 certification; RoHS and REACH declarations are available through Siemens Industry Online Support.