SENTRON 3VA1196-3ED26-0AF0 — 16 A, 2-Pole MCCB with TM210 Release
Its interrupting capacity reaches 75.6 kA at 240 V AC and 52.5 kA at 415 V AC, per the datasheet — figures that govern its fault-clearing capability in low-voltage distribution panels.
At 60 °C and 65 °C the continuous current derates to 15 A; at 70 °C it remains at 15 A.
Panel Integration and Auxiliary Switching
Footprint is 70 mm deep, 50.8 mm wide (2 DIN modules), 130 mm tall — mounts on standard DIN rail within an IP40 front-protected enclosure. A separate basic switch variant (3VA11963ED260AA0) is the underlying switching mechanism.