Skip to main content
Siemens 3VA1196-3EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-3EE32-0AA0 SENTRON MCCB, 16 A, 3-Pole, 75.6

MPN3VA1196-3EE32-0AA0
Active

Siemens SENTRON 3VA1196-3EE32-0AA0, molded case circuit breaker, 3-pole, 16 A, TM220 release, breaking capacity 75.6 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1196-3EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1196-3EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W
3VA1196-3EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1196-3EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1196-3EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1196-3EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1196-3EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB carries on a shipboard switchboard

Its breaking capacity reaches 75.6 kA at 240 V AC and 52.5 kA at 415 V AC, which means it can safely interrupt fault currents up to those levels without cascading upstream — essential for selectivity studies on a vessel's main switchboard or emergency distribution board.

At 440 V AC the interrupting rating is 32 kA, dropping to 11.9 kA at 500 V and 690 V AC. That voltage-dependent curve is typical for MCCBs, but critical when the breaker is applied near the transformer secondary on a 480 V or 690 V shipboard system — the available fault current must be coordinated with the breaker's rating at that specific voltage. The thermal-magnetic TM220 release holds 16 A from 40 °C through 55 °C, then derates to 15 A at 60 °C through 70 °C. In a hot machinery space or unventilated panel, that 1 A drop can mean the difference between nuisance tripping and a stable feed.

Sourcing and procurement note

Frequently asked questions

What is the breaking capacity of this MCCB at 240 V?

The breaking capacity is 75.6 kA at 240 V AC, sufficient for high-fault-current applications near large transformers.

What is the rated current and how does it derate with temperature?

Rated current is 16 A from 40 °C to 55 °C, then derates to 15 A at 60 °C through 70 °C.

Does this breaker include ground-fault monitoring or communication?

No, it is without ground-fault monitoring and without communication function — a basic thermal-magnetic line protection device.

Where can I buy 3VA1196-3EE32-0AA0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
3VA1196-3EE32-0AA0