It carries a continuous current rating of 16 A up to 55 °C, derating to 15 A at 60–70 °C — so in a warm enclosure you lose 1 A above 55 °C. The interrupting capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V. That makes it a straight replacement for existing fixed-trip MCCB slots where you don't need adjustable pickup or ground-fault monitoring. No undervoltage release, no communication module, no trip indicator on the front.
Dimensions are 76.2 mm wide, 130 mm tall, 70 mm deep — a standard 3-pole MCCB footprint for a 16 A frame.