Breaking capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V, covering most industrial distribution panels up to 690 V line-to-line. Thermal derating is flat to 50 °C at 16 A, then steps down to 15.36 A at 55 °C, 15.04 A at 60 °C, 14.72 A at 65 °C, and 14.4 A at 70 °C.
Integration Notes
IP40 on the front — suitable for clean indoor panels; not rated for washdown environments. The TM240 release has a fixed thermal time delay (tr max. 1 s at 6× Iu per the spec). No phase-failure detection inside — if that's required, add an external phase monitor or step up to a 3VA variant with electronic release.
Designed to IEC 60947-2 (MCCB standard). The manufacturer provides RoHS and REACH declarations as standard; UL/CSA listing depends on the specific variant — verify the nameplate marking for the exact certification marks on the unit received.