Skip to main content
Siemens 3VA1196-4ED12-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-4ED12-0AA0 SENTRON MCCB, 16 A, 1-Pole, TM210

MPN3VA1196-4ED12-0AA0
Active

Siemens SENTRON 3VA1 series, Molded case circuit breaker (MCCB), 3VA1196-4ED12-0AA0, 1-pole, 16 A rated at 40 °C, TM210 thermal-magnetic release, 75.6 kA breaking capacity at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1196-4ED12-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1196-4ED12-0AA0 — Ratings
ParameterValue
Number of poles1
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classS
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V9 kA
Power loss, max.3.53 W

Protection & Trip Unit

3VA1196-4ED12-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1196-4ED12-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1196-4ED12-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1196-4ED12-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1196-4ED12-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.12 in
Width (in)1 in
Depth (in)2.76 in

Product details

The Siemens 3VA1196-4ED12-0AA0 is a SENTRON 3VA1 molded case circuit breaker (MCCB) designed for line protection in a 1-pole configuration. It carries a continuous current rating of 16 A at 40 °C (derating to 15 A at 60 °C and above), with a TM210 thermal-magnetic release that provides fixed overload and short-circuit protection curves suited for feeder and branch circuits in industrial panels.

Breaking capacity and selectivity

The interrupting rating is 75.6 kA at 240 V AC and 9 kA at 415 V AC — a wide gap that tells you this breaker is optimized for 240 V line-to-neutral or line-to-ground fault duty typical in North American split-phase panels, not for 400 V three-phase feeders where the 9 kA figure governs. At 415 V the 9 kA SCCR is modest; coordinate downstream to avoid cascading trip if fault current exceeds that level. Rated insulation voltage is 500 V, and the operating voltage at AC is 415 V, so the breaker is electrically rated for 400 V-class systems but the interrupting capacity at that voltage is the limiting factor for fault handling.

Physical fit and panel integration

Width is 25.4 mm (1 inch) — a single pole module that snaps onto standard DIN rail. Depth is 70 mm, height 130 mm. The front face carries IP40 protection, meaning tools and fingers are kept out but the enclosure is not sealed against moisture; mount inside a rated panel for washdown or outdoor environments.

Frequently asked questions

What is the breaking capacity of 3VA1196-4ED12-0AA0 at 240 V?

75.6 kA at 240 V AC, which is the headline interrupting rating for this 1-pole breaker.

What is the width of 3VA1196-4ED12-0AA0?

25.4 mm (1 inch), a single-pole module width for DIN-rail mounting.

Where can I buy 3VA1196-4ED12-0AA0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
3VA1196-4ED12-0AA0