1-pole SENTRON MCCB with TM210 release
Its 75.6 kA breaking capacity at 240 V AC handles high-fault scenarios typical of industrial distribution panels; at 415 V AC the rating drops to 9 kA, which still covers most secondary feeder faults in a 400 V system. The single-pole form factor (25.4 mm wide) fits standard DIN-rail or panel-mount enclosures where branch-circuit protection is needed without occupying multiple module slots.
Thermal-magnetic curve and derating
The TM210 release holds the full 16 A rating from 40 °C up to 55 °C, then derates to 15 A at 60 °C through 70 °C. That flat thermal curve means the breaker can be applied in a warm cabinet without losing capacity until the ambient exceeds 55 °C. Maximum power loss is 3.53 W, low enough to avoid significant heat buildup inside a sealed enclosure.
Physical integration
At 70 mm deep, 25.4 mm wide, and 130 mm tall, the 3VA1196-4ED16-0AA0 occupies a single-pole width on the DIN rail.