Skip to main content
Siemens 3VA1196-4EF32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-4EF32-0AC0 SENTRON MCCB, 16 A, 121 kA at 240

MPN3VA1196-4EF32-0AC0

Siemens SENTRON 3VA1196-4EF32-0AC0, molded case circuit breaker, 3-pole, 16 A, TM240 release, 121 kA at 240 V, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1196-4EF32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1196-4EF32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C15.36 A
Current at 60 °C15.04 A
Current at 65 °C14.72 A
Current at 70 °C14.4 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1196-4EF32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1196-4EF32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1196-4EF32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1196-4EF32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1196-4EF32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1196-4EF32-0AC0 is a SENTRON molded case circuit breaker (MCCB) for line protection, rated 16 A continuous current with a TM240 thermal-magnetic release. Its breaking capacity hits 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — so it handles high-fault scenarios across common industrial voltages without cascading upstream. The 800 V rated insulation voltage (Ui) gives headroom for 480/600 V panels. The 3-pole design carries 2 auxiliary switches (HQ type) for status feedback to a PLC or annunciator. No undervoltage release, no ground-fault monitoring, no communication module — this is a straight line-protection MCCB with a TM240 trip unit, adjustable response time up to 1 s.

Thermal derating and panel fit

The 16 A rating holds flat from 40 °C to 50 °C; above that it derates linearly to 14.4 A at 70 °C. If the panel ambient runs hot — say near a drive or transformer — the effective current drops, so size the branch circuit for the derated value, not the nameplate. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth. The 76.2 mm width (3-inch pitch) fits standard MCCB panel cutouts and bus-bar spacing. IP40 on the front means it's protected against solid objects >1 mm but not washdown — keep it inside a dry enclosure.

Frequently asked questions

What is the breaking capacity of 3VA1196-4EF32-0AC0 at 415 V?

75.6 kA at 415 V. At 240 V it's 121 kA, at 440 V it's 52.5 kA, and at 690 V it's 11.9 kA.

Where can I buy 3VA1196-4EF32-0AC0?

This part is sourced to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the rated current of 3VA1196-4EF32-0AC0?

The rated continuous current Iu is 16 A, holding flat from 40 °C to 50 °C and derating to 14.4 A at 70 °C.

Does 3VA1196-4EF32-0AC0 include auxiliary contacts?

Yes, it comes with 2 auxiliary switches (HQ type) for status feedback. No undervoltage release or ground-fault monitoring is fitted.

MPN
3VA1196-4EF32-0AC0