Siemens SENTRON 3VA1196-4EF36-0AF0 — 16 A MCCB with TM240 trip and 121 kA SCCR
Its thermal-magnetic trip unit (TM240) provides fixed thermal and magnetic protection without voltage-trigger or ground-fault monitoring — a straightforward overcurrent-only device suited for feeder and branch-circuit duty in distribution panels. The interrupting ratings are substantial: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V, giving the breaker headroom for high-fault installations without cascading upstream.
Above that, derating is linear: 15.36 A at 55 °C, 15.04 A at 60 °C, 14.72 A at 65 °C, and 14.4 A at 70 °C. Physical footprint is 76.2 mm wide × 130 mm tall × 70 mm deep, which is the standard SENTRON 3VA three-pole form factor for DIN-rail or screw-fixed backplate installation.