Siemens 3VA1196-5EF32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-5EF32-0AG0 Circuit Breaker, 55kA @ 415V, 16A

MPN3VA1196-5EF32-0AG0

Siemens 3VA1 IEC frame 160 circuit breaker, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection TM240, In=16A, overload Ir=11A…16A, short-circuit Ii=10…20 x In, with nut keeper kit, 1 auxiliary switch HP, 1 trip alarm switch HP.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What the ratings mean for your panel

The Siemens 3VA1196-5EF32-0AG0 is a 3-pole IEC frame 160 molded-case circuit breaker with a 55 kA interrupting capacity at 415 V (class M). That 55 kA rating means it can safely clear a fault up to that level without rupturing or cascading upstream — critical for high-fault-capacity installations like transformer secondaries or large motor control centers. The TM240 thermal-magnetic trip unit gives you adjustable overload protection (Ir = 11 A to 16 A) and fixed short-circuit protection (Ii = 10 to 20 × In, so 160 A to 320 A at the 16 A rating). The built-in nut keeper kit, one auxiliary switch (HP), and one trip alarm switch (HP) reduce field wiring — you don't need separate add-on modules for status feedback to the PLC or alarm annunciation.

Panel integration notes

Mounts in a standard IEC frame 160 footprint — the same cut-out and bus-bar spacing as other 3VA1 breakers. The nut keeper kit retains the terminal screws during wiring, a small time-saver on a multi-breaker panel. The auxiliary and alarm switches are pre-installed and wired to the breaker's internal contacts; verify the wiring diagram for your PLC input voltage before energizing.

Frequently asked questions

What is the breaking capacity of this breaker?

The breaking capacity is 55 kA at 415 V (class M) per IEC 60947-2. That is the maximum fault current it can safely interrupt at that voltage.

What does the TM240 trip unit adjust to?

Overload protection (Ir) is adjustable from 11 A to 16 A. Short-circuit protection (Ii) is fixed at 10 to 20 times In, so 160 A to 320 A at the 16 A setting.

Where can I buy 3VA1196-5EF32-0AG0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.