Skip to main content
Siemens 3VA1196-5EF32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-5EF32-0HA0 SENTRON MCCB, 16 A, 187 kA IC

MPN3VA1196-5EF32-0HA0

Siemens SENTRON 3VA1196-5EF32-0HA0, molded case circuit breaker, 3-pole, 16 A rated current, 187 kA breaking capacity at 240 V AC, line protection design, with shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1196-5EF32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11965EF320AA0

Ratings

3VA1196-5EF32-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1196-5EF32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1196-5EF32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1196-5EF32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1196-5EF32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1196-5EF32-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VA1 MCCB — 16 A, 187 kA IC, with Shunt Trip

The 3VA1196-5EF32-0HA0: This variant ships with a shunt trip release (STL) for remote tripping — wired to an E-stop or safety relay, it drops the breaker on command without a handle throw. The overcurrent release is the TM240 thermal-magnetic type, so it handles overload and short-circuit protection in one device. No undervoltage release, no ground-fault monitoring, no communication module on this order code; it's a straightforward power breaker with remote trip capability.

Panel Fit and Mounting

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a 3-pole frame that fits standard MCCB mounting footprints in distribution boards. The 800 V rated insulation voltage gives headroom for 480 V and 600 V class systems without derating the dielectric. Power loss is 10.6 W maximum, so ventilation in a sealed enclosure is manageable but not negligible if multiple breakers are ganged.

Frequently asked questions

What is the breaking capacity of 3VA1196-5EF32-0HA0 at 240 V?

187 kA at 240 V AC. At 415 V it's 121 kA, at 440 V it's 75.6 kA, and at 500 V or 690 V it holds 17 kA.

What does the shunt trip release on this MCCB do?

The shunt trip (STL) allows remote tripping by applying a control voltage to the release coil — useful for E-stop circuits or safety relay integration. This variant does not include an undervoltage release.

Where can I buy 3VA1196-5EF32-0HA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

MPN
3VA1196-5EF32-0HA0