Skip to main content
Siemens 3VA1196-5EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-5EF36-0JA0 SENTRON MCCB, 16 A, 3-Pole, 187 k

MPN3VA1196-5EF36-0JA0

Siemens SENTRON 3VA1196-5EF36-0JA0, molded case circuit breaker, 3-pole, 16 A, TM240 thermal-magnetic release, line protection, 187 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1196-5EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1196-5EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C15.36 A
Current at 60 °C15.04 A
Current at 65 °C14.72 A
Current at 70 °C14.4 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1196-5EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1196-5EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1196-5EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1196-5EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1196-5EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SCCR and thermal derating — what the ratings mean

The 3VA1196-5EF36-0JA0: The interrupting ratings are the standout: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. At 240 V this breaker clears a 187 kA fault without cascading upstream — that is a high-fault-capacity MCCB for transformer secondaries or large motor control centers where available fault current exceeds 100 kA. The 690 V rating (17 kA) confirms it can serve 690 V industrial grids, though the 440 V figure (75.6 kA) is the more common threshold for North American 480 V systems. Thermally, the 16 A rating holds flat from 40 °C through 50 °C; above that it derates linearly to 14.4 A at 70 °C. If the panel ambient runs above 50 °C, the breaker must be applied at the derated current — a point often missed in BOM planning.

Physical fit and panel integration

The 3VA1196-5EF36-0JA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA frame size that mounts on a DIN rail or directly to a backplate via the integral latching mechanism. The 76.2 mm width (3 inches) occupies three 25.4 mm module positions on a DIN rail, matching the 3-pole footprint. Front protection is IP40, so the breaker face is protected against tools and small solids but not against water ingress — suitable for enclosed panel mounting, not washdown environments. The -25 °C to 70 °C operating range covers most indoor industrial enclosures, and the -40 °C to 80 °C storage range accommodates cold warehouse or transport conditions.

Frequently asked questions

Where can I buy 3VA1196-5EF36-0JA0?

This part is sourced and quoted to order against an RFQ through independent industrial automation distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What is the interrupting rating of 3VA1196-5EF36-0JA0 at 240 V?

The interrupting rating is 187 kA at 240 V, with 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. These are the maximum fault currents the breaker can safely clear at each voltage level.

Does 3VA1196-5EF36-0JA0 include a shunt trip?

The auxiliary release design is a shunt trip (STL) with integrated auxiliary trip 3VA9688-0BL32, but the breaker ships without an undervoltage release or auxiliary contact version as standard. The shunt trip is available as an option.

What is the thermal derating for 3VA1196-5EF36-0JA0 above 50 °C?

The 16 A rating holds flat from 40 °C to 50 °C. Above 50 °C it derates: 15.36 A at 55 °C, 15.04 A at 60 °C, 14.72 A at 65 °C, and 14.4 A at 70 °C. Apply the derated value if the panel ambient exceeds 50 °C.

MPN