At 415 V the rating drops to 154 kA, at 440 V to 121 kA, and at 500 V or 690 V it holds at 17 kA — the steep fall-off above 440 V is typical of a compact MCCB frame and matters if your secondary is a 480 V or 600 V class transformer. That keeps the BOM simple and the part interchangeable with older panels that expect a non-electronic MCCB.
No official successor order code has been published for this part; the 3VA1 platform remains the current SENTRON MCCB generation for line-protection applications.
The 3VA1196-6ED32-0AA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole MCCB footprint that drops into standard SENTRON 3VA1 mounting bases and busbar systems.
Ambient derating and operating range
The 16 A rating holds flat from 40 °C through 55 °C; at 60 °C it derates to 15 A and stays there through 70 °C. That means no capacity loss in most ventilated panels, but a sealed enclosure near other heat sources may push the effective rating down. The storage minimum is the more restrictive number for warehousing — keep it above -40 °C and the breaker will not suffer mechanical damage before installation.