Skip to main content
Siemens 3VA1196-6EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-6EE32-0AA0 SENTRON MCCB, 16 A, 220 kA at 240

MPN3VA1196-6EE32-0AA0
Active

Siemens SENTRON 3VA1 series, molded case circuit breaker (MCCB), 3VA1196-6EE32-0AA0, 3-pole, 16 A, breaking capacity 220 kA at 240 V AC, TM220 thermal-magnetic trip unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1196-6EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1196-6EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.6 W
3VA1196-6EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1196-6EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1196-6EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1196-6EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1196-6EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The breaker carries a 220 kA breaking capacity at 240 V AC, which drops to 154 kA at 415 V and 121 kA at 440 V, so it handles high fault-current scenarios common in industrial main feeders or large sub-distribution boards.

At 415 V it still delivers 154 kA, and at 690 V it holds 17 kA, so it remains usable in 400 V class systems with substantial transformer capacity.

Thermal performance and derating

At 60 °C it derates to 15 A, and at 70 °C it stays at 15 A, so a panel near a heat source or in a hot climate still delivers 15 A continuous. Maximum power loss is 10.6 W, which is modest for a 3-pole MCCB of this class and helps keep internal cabinet temperatures manageable.

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint that fits most Siemens SENTRON mounting bases and panel cutouts.

It is a standard catalog item in the SENTRON 3VA1 family.

Frequently asked questions

Where can I buy 3VA1196-6EE32-0AA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 240 V?

The 3VA1196-6EE32-0AA0 has a 220 kA breaking capacity at 240 V AC, dropping to 154 kA at 415 V and 121 kA at 440 V.

Does this breaker have a thermal-magnetic or electronic trip unit?

It uses a TM220 thermal-magnetic trip unit — fixed thermal and magnetic settings, no electronic adjustment or communication function.

MPN
3VA1196-6EE32-0AA0