Skip to main content
Siemens 3VA1196-6EF32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-6EF32-0AF0 SENTRON MCCB, 16 A, 220 kA at 240

MPN3VA1196-6EF32-0AF0

Siemens SENTRON 3VA1196-6EF32-0AF0, 3-pole molded case circuit breaker, line protection, 16 A rated continuous current, TM240 overcurrent release, 220 kA interrupting capacity at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1196-6EF32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1196-6EF32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C15.36 A
Current at 60 °C15.04 A
Current at 65 °C14.72 A
Current at 70 °C14.4 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1196-6EF32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1196-6EF32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1196-6EF32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1196-6EF32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1196-6EF32-0AF0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens SENTRON 3VA1196-6EF32-0AF0 — 16 A MCCB with TM240 Release

The Siemens SENTRON 3VA1196-6EF32-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a rated continuous current Iu of 16 A and a rated insulation voltage Ui of 800 V. Its interrupting capacity hits 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — numbers that tell you it's built for high-fault panels where a standard MCCB would weld its contacts shut. The TM240 overcurrent release is fixed, not adjustable for long-time pickup, so the 16 A rating is a hard ceiling — no dialing it up for a temporary overload.

Thermal Derating and Ambient Reality

The 16 A rating holds flat from 40 °C through 50 °C, then starts a gentle slide: 15.36 A at 55 °C, 15.04 A at 60 °C, 14.72 A at 65 °C, and 14.4 A at 70 °C. If your panel runs hot — say a crowded enclosure near a drive — that 14.4 A at 70 °C is the real trip threshold, not the nameplate 16 A. Plan your load accordingly.

Mounting and Integration

The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that drops into a SENTRON panelboard or a DIN-rail adapter without surprises. Front face is IP40 rated, so it's fine inside a closed panel but not for washdown zones. It ships with one auxiliary switch and one trip alarm switch (HQ type) — useful for feeding a status signal back to a PLC or annunciator without adding a separate contact block.

MPN
3VA1196-6EF32-0AF0