Skip to main content
Siemens 3VA1196-6EF32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-6EF32-0CA0 SENTRON MCCB, 16 A, 220 kA at 240

MPN3VA1196-6EF32-0CA0

Siemens SENTRON 3VA1196-6EF32-0CA0, molded case circuit breaker, 3-pole, 16 A rated current, 220 kA breaking capacity at 240 VAC, TM240 thermal-magnetic release, undervoltage release included.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1196-6EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11966EF320AA0
3VA1196-6EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.13.1 W
3VA1196-6EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1196-6EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1196-6EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1196-6EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1196-6EF32-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1196-6EF32-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated for 16 A continuous current at 40 °C, with a TM240 thermal-magnetic overcurrent release and an integrated undervoltage release (UVR). Its interrupting rating reaches 220 kA at 240 VAC, 154 kA at 415 VAC, and 121 kA at 440 VAC — figures that place it squarely in high-fault-duty distribution panels where upstream transformer capacity or parallel-feed sources drive available fault current above 100 kA.

Mounting and integration — panel fit

Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth — a standard SENTRON 3VA1 frame size that mounts via screw terminals to a backplate or DIN rail adapter. The 3-pole block occupies roughly 3 inches of panel width; plan for bending-radius clearance on the line and load lugs, particularly when routing 16 A branch circuits in a crowded enclosure. Operating temperature range is -25 °C to 70 °C, with full 16 A rating maintained up to 55 °C; above that, derate to 15 A at 60–70 °C.

The breaker ships with the undervoltage release factory-installed (design designation UVR), so no field-fit kit is required for that function.

Frequently asked questions

What does the TM240 release designation mean?

TM240 indicates a thermal-magnetic overcurrent release with fixed settings — thermal element for overload protection and magnetic element for short-circuit protection, calibrated for line (distribution) duty.

Does this breaker include an undervoltage release?

Yes, the design includes an undervoltage release (UVR) as the auxiliary release — it will trip the breaker when supply voltage drops below a set threshold.

MPN
3VA1196-6EF32-0CA0