3VA1196-6EF32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11966EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1196-6EF32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.6 W
3VA1196-6EF32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1196-6EF32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1196-6EF32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1196-6EF32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1196-6EF32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

16 A MCCB with 220 kA interrupting capacity — line protection for high-fault panels

The Siemens SENTRON 3VA1196-6EF32-0KC0 is a 3-pole molded case circuit breaker rated for line protection, carrying a continuous current of 16 A across its operating temperature range from -25 °C to 70 °C, with a slight derating to 15 A above 60 °C. Its interrupting capacity reaches 220 kA at 240 VAC, 154 kA at 415 V, and 121 kA at 440 V — figures that place it in the high-fault-current class for industrial main feeders or large sub-distribution boards where upstream transformer capacity drives available fault current above 100 kA. This breaker ships with a factory-fitted shunt trip release and two auxiliary switches (HQ design), so it arrives ready for remote tripping and status feedback without additional accessory assembly. The shunt trip allows a safety PLC or emergency-stop circuit to open the breaker directly — useful for machinery isolation or process interlock schemes. The auxiliary switches provide normally-open and normally-closed contacts for panel indication or upstream control logic.

At 76.2 mm wide, 130 mm tall, and 70 mm deep, the 3VA1196-6EF32-0KC0 occupies a standard 3-pole MCCB footprint on the DIN rail or mounting plate.

Comparison with 3VA1110-5ED36-0AC0

Compared to the 3VA1110-5ED36-0AC0, this 3VA1196-6EF32-0KC0 is a different frame size and rating class. The 3VA1110 series typically covers lower current ranges (10–16 A) in a narrower physical package. The 3VA1196 frame here is physically larger (76.2 mm vs roughly 54 mm width) and carries the higher interrupting capacity needed for main breaker duty. They are not drop-in interchangeable — a panel laid out for the 3VA1110 would need re-drilling of mounting holes and re-routing of bus bars to accept this wider frame. For a like-for-like replacement in an existing 3VA1110 cutout, stay with that series.

Frequently asked questions

Where can I buy 3VA1196-6EF32-0KC0 and what is the lead time?

This part is available to order through our distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

What is the breaking capacity of 3VA1196-6EF32-0KC0 at different voltages?

The interrupting capacity is 220 kA at 240 VAC, 154 kA at 415 VAC, 121 kA at 440 VAC, and 17 kA at both 500 VAC and 690 VAC. These ratings make it suitable for high-fault-current applications where available fault current exceeds 100 kA.

What accessories are fitted on 3VA1196-6EF32-0KC0?

It comes with a shunt trip release for remote tripping and two auxiliary switches (HQ design) for status feedback. No undervoltage release or ground-fault monitoring is included on this variant.

What is the rated current of 3VA1196-6EF32-0KC0 at elevated temperatures?

The breaker is rated 16 A continuously from -25 °C up to 55 °C. At 60 °C and above, it derates to 15 A. This thermal behavior must be accounted for in sealed enclosures with multiple heat sources.