Siemens 3VA1196-6GD42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1196-6GD42-0AA0 SENTRON MCCB, 4-pole, 16 A, 220 k

MPN3VA1196-6GD42-0AA0
Active

Siemens SENTRON 3VA1196-6GD42-0AA0, 4-pole molded case circuit breaker, 16 A rated continuous current, 220 kA interrupting at 240 V, TM210 release, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1196-6GD42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1196-6GD42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.6 W
3VA1196-6GD42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1196-6GD42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1196-6GD42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1196-6GD42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1196-6GD42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.1 in
Width (in)4 in
Depth (in)2.8 in

Product details

Its interrupting capacity hits 220 kA at 240 V, dropping to 154 kA at 415 V and 121 kA at 440 V — numbers that matter when you're protecting a high-fault panel feeding a transformer or a large motor branch.

At 70 mm deep, 101.6 mm wide, and 130 mm tall, this MCCB fits standard panel-mount cutouts for 4-pole breakers in the 16 A class.

Rated continuous current holds at 16 A from 40 °C up to 55 °C, then derates to 15 A at 60 °C and 65 °C, and stays at 15 A up to 70 °C. That's a flat thermal curve — no surprise drop at 50 °C, which simplifies panel sizing in warm cabinets. Maximum power loss is 10.6 W.

Listed as current production. The 3VA1196-6GD42-0AA0 is a line-protection variant with no communication module and no ground-fault monitoring — a straight thermal-magnetic MCCB for standard distribution.

Frequently asked questions

What is the interrupting capacity of 3VA1196-6GD42-0AA0 at common voltages?

220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V or 690 V.

Where can I buy 3VA1196-6GD42-0AA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
3VA1196-6GD42-0AA0