Skip to main content
Siemens 3VA1216-4EE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-4EE42-0AA0 SENTRON MCCB, 160 A, 4-Pole, 121

MPN3VA1216-4EE42-0AA0

Siemens SENTRON 3VA, molded case circuit breaker, line protection, 4-pole, 160 A, TM220 release, breaking capacity 121 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1216-4EE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1216-4EE42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C156 A
Current at 60 °C151 A
Current at 65 °C147 A
Current at 70 °C142 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.33 W
3VA1216-4EE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1216-4EE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-4EE42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1216-4EE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-4EE42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

SENTRON 3VA, 160 A, 4-Pole MCCB — Line Protection with TM220 Release

The Siemens 3VA1216-4EE42-0AA0 is a SENTRON-series molded case circuit breaker (MCCB) designed for line protection, carrying a 160 A rated current at 40 °C and a TM220 thermal-magnetic overcurrent release. Breaking capacity sits at 121 kA at 240 V and 75.6 kA at 415 V — figures that cover high-fault utility feeds and industrial transformer secondaries without cascading upstream. At 690 V the breaker still interrupts 11.9 kA, enough for most 690 V motor circuits. Rated insulation voltage is 800 V, so the 3VA1216-4EE42-0AA0 is suitable for 690 V systems with margin.

The 160 A rating holds from 40 °C through 50 °C. Above 55 °C the breaker derates: 156 A at 55 °C, 151 A at 60 °C, 147 A at 65 °C, and 142 A at 70 °C. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Dimensions are 70 mm deep, 140 mm wide, 158 mm high. The 140 mm width is standard for a 4-pole MCCB in the SENTRON 3VA platform — fits existing 3VA busbar and mounting-foot patterns without adapter plates.

Frequently asked questions

Where can I buy 3VA1216-4EE42-0AA0 and get a price?

Sourced through independent distribution channels. Submit an RFQ; availability and current pricing are confirmed at quote time — no online stock figure replaces a live quote.

What is the breaking capacity of 3VA1216-4EE42-0AA0 at 415 V?

75.6 kA at 415 V. At 240 V it reaches 121 kA; at 690 V it still interrupts 11.9 kA.

What is the rated current of 3VA1216-4EE42-0AA0?

160 A at 40 °C through 50 °C. Derates above 55 °C — see the thermal table in the spec section.

What is the overcurrent release type on this MCCB?

TM220 — a thermal-magnetic release. Fixed thermal pickup, magnetic short-circuit trip. No electronic adjustment or communication function on this variant.

MPN