Siemens 3VA1216-4EF32-0AA0 SENTRON MCCB, 160 A, 3-Pole, TM24

MPN3VA1216-4EF32-0AA0
Active

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA1216-4EF32-0AA0, 3-pole, 160 A (40 °C), TM240 release, 121 kA at 240 V.

$293.37Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1216-4EF32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1216-4EF32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C156 A
Current at 60 °C151 A
Current at 65 °C147 A
Current at 70 °C142 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.33 W
3VA1216-4EF32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1216-4EF32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-4EF32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1216-4EF32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-4EF32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width105 mm
Depth70 mm
Height (in)6.22 in
Width (in)4.13 in
Depth (in)2.76 in

Product details

The Siemens 3VA1216-4EF32-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated 160 A at 40 °C, 3-pole, with a TM240 thermal-magnetic overcurrent release. The interrupting rating is 121 kA at 240 V AC, dropping to 75.6 kA at 415 V, 52.5 kA at 440 V, 17 kA at 500 V, and 11.9 kA at 690 V — figures that govern its SCCR in a given panel.

Thermal derating and release type

The TM240 release holds 160 A continuously up to 50 °C ambient. Above that, derating applies: 156 A at 55 °C, 151 A at 60 °C, 147 A at 65 °C, and 142 A at 70 °C. The TM240 designation indicates a thermal-magnetic trip unit with a 240 A frame rating — the breaker's continuous current rating is set by the installed trip coil or electronic module, here 160 A.

MPN