MCCB for line protection with UVR
Its interrupting capacity reaches 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V — numbers that tell you the fault-clearing headroom at your service voltage without cascading upstream.
Derating begins at 55 °C (155.6 A), dropping to 142.4 A at 70 °C.
The integrated auxiliary trip order code is 3VA9608-0BB11 — order that separately if you need a shunt trip or additional alarm contact. Front face protection is IP40, adequate for a clean indoor panel.