Skip to main content
Siemens 3VA1216-4EF32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-4EF32-0CH0 SENTRON MCCB, 160 A, 3-Pole, Line

MPN3VA1216-4EF32-0CH0

Siemens SENTRON 3VA1216-4EF32-0CH0, 3-pole molded case circuit breaker, 160 A rated continuous current, line protection version with TM240 thermal-magnetic overcurrent release, 121 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1216-4EF32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1216-4EF32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C155.6 A
Current at 60 °C151.2 A
Current at 65 °C146.8 A
Current at 70 °C142.4 A
Switching capacity classN
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA
3VA1216-4EF32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1216-4EF32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-4EF32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1216-4EF32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-4EF32-0CH0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1216-4EF32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current at 40 °C, with a TM240 thermal-magnetic overcurrent release that handles both overload and short-circuit protection in one device. Its breaking capacity hits 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V — so it can sit on the secondary side of a distribution transformer or feed a high-fault panelboard without cascading upstream. If you're replacing a breaker in a feeder panel or a main disconnect, this is the right class. The front face carries a trip indicator so a quick visual scan tells you if it's tripped on fault vs. manually switched off — saves time on a troubleshooting walk.

Current derating and thermal reality

Above that it starts to step down: 155.6 A at 55 °C, 151.2 A at 60 °C, 146.8 A at 65 °C, 142.4 A at 70 °C.

Dimensions are 105 mm wide, 158 mm high, 70 mm deep. Mounting is via the rear screw terminals or optional DIN-rail adapter; the terminals accept copper or aluminum conductors sized for 160 A.

Frequently asked questions

What is the breaking capacity of 3VA1216-4EF32-0CH0 at 415 V?

The breaking capacity is 75.6 kA at 415 V AC. It also carries 121 kA at 240 V, 25 kA at 440 V, and 11.9 kA at 690 V.

Where can I buy 3VA1216-4EF32-0CH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Does this MCCB include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as standard, plus a 2-auxiliary + 1 trip alarm switch block (HQ version) for remote status indication.

What is the rated continuous current of 3VA1216-4EF32-0CH0?

The rated continuous current Iu is 160 A at 40 °C ambient. It derates to 142.4 A at 70 °C ambient.

MPN