Skip to main content
Siemens 3VA1216-4EF32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1216-4EF32-0DA0 MCCB, 160 A, 121 kA at 24

MPN3VA1216-4EF32-0DA0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA1216-4EF32-0DA0, 160 A rated continuous current, 3-pole, line protection version with TM240 thermal-magnetic release and integrated undervoltage release.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1216-4EF32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1216-4EF32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C155.6 A
Current at 60 °C151.2 A
Current at 65 °C146.8 A
Current at 70 °C142.4 A
Switching capacity classN
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA
3VA1216-4EF32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1216-4EF32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-4EF32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1216-4EF32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-4EF32-0DA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

Siemens SENTRON 3VA1216-4EF32-0DA0 is a 3-pole molded case circuit breaker rated for 160 A continuous current (Iu) at 40 °C, with a TM240 thermal-magnetic overcurrent release. Breaking capacity runs 121 kA at 240 V AC, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V — so the 240 V rating is the headline number, but the 415 V figure is what governs in most European 400 V distribution panels. At 690 V the capacity drops to 11.9 kA, which still clears most industrial fault levels below 12 kA. An integrated undervoltage release (UVR) is fitted as standard — part number 3VA9608-0BB25 for the auxiliary trip assembly. If you need those, you are looking at a different suffix.

Current derating — the real-world number

At 55 °C it derates to 155.6 A, at 60 °C to 151.2 A, at 65 °C to 146.8 A, and at 70 °C to 142.4 A.

Dimensions: 105 mm wide, 158 mm high, 70 mm deep.

MPN