Skip to main content
Siemens 3VA1216-5EE42-0AA0-ZD00 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-5EE42-0AA0-ZD00 Circuit Breaker, 160A, 55kA

MPN3VA1216-5EE42-0AA0-ZD00

Siemens 3VA1 IEC frame 250, 4-pole circuit breaker, breaking capacity class M, Icu=55kA @ 415V, In=160A, TM220, ATFM, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The Siemens 3VA1216-5EE42-0AA0-ZD00 is a 4-pole IEC frame 250 circuit breaker in the 3VA1 series, rated at In=160A with a breaking capacity Icu=55kA @ 415V (class M). It carries a TM220 thermal-magnetic trip unit with ATFM (Adjustable Thermal Fixed Magnetic) — overload protection Ir adjustable from 112A to 160A, short-circuit protection fixed at Ii=10 x In. This order code is configured for a DC Power OEM in China.

The 55kA Icu at 415V places this breaker in breaking capacity class M — suitable for industrial panelboards and distribution systems with moderate fault current levels, such as those fed by a transformer in the 1000-2000 kVA range. The TM220 trip unit with ATFM gives you adjustable thermal protection (Ir 112A-160A) for cable or busbar protection, while the fixed magnetic pickup at 10x In (1600A) clears hard shorts fast.

Integration Notes

This is a 4-pole DIN-rail mountable breaker in the 3VA1 frame — fits standard Siemens panelboard and distribution board footprints. The unprotected N conductor should be wired to a solid neutral bus, not through the breaker poles. Verify that the fixed Ii=10xIn setting coordinates with downstream breakers for selectivity — the high magnetic pickup may require careful grading with branch-circuit MCBs.

Frequently asked questions

Where can I buy 3VA1216-5EE42-0AA0-ZD00 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is the breaking capacity of this breaker?

The Icu is 55kA at 415V, which is breaking capacity class M per the IEC 60947-2 standard.

What does the TM220 ATFM trip unit mean?

TM220 indicates a thermal-magnetic trip unit; ATFM means Adjustable Thermal Fixed Magnetic — overload protection Ir is adjustable from 112A to 160A, while short-circuit protection Ii is fixed at 10x In (1600A).

Is the neutral conductor protected on this variant?

No, the N conductor is unprotected on this order code — it is a 3-pole + N configuration where the neutral is not switched or protected.

MPN