Skip to main content
Siemens 3VA1216-5EF32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-5EF32-0AD0 SENTRON MCCB, 160 A, 3-Pole, TM24

MPN3VA1216-5EF32-0AD0

Siemens SENTRON 3VA1216-5EF32-0AD0, molded case circuit breaker, 3-pole, TM240 thermal-magnetic release, 160 A at 40 °C, line protection, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1216-5EF32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12165EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1216-5EF32-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C156 A
Current at 60 °C151 A
Current at 65 °C147 A
Current at 70 °C142 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.33 W
3VA1216-5EF32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1216-5EF32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-5EF32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1216-5EF32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-5EF32-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width105 mm
Depth70 mm
Height (in)6.22 in
Width (in)4.13 in
Depth (in)2.76 in

Product details

The Siemens 3VA1216-5EF32-0AD0 is a SENTRON 3-pole molded case circuit breaker rated 160 A at 40 °C, with a TM240 thermal-magnetic release designed for line protection. That TM240 designation means the thermal trip is fixed at 160 A (the frame rating), and the magnetic short-circuit pickup is adjustable — typical for feeder protection where you need coordination downstream. The interrupting ratings are substantial: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V, so this breaker can handle high-fault-current scenarios like transformer secondaries or large motor control centers without cascading failure upstream.

Mounting dimensions and panel fit

The 70 mm depth leaves room for rear-connected busbars or a separate shunt-trip accessory.

Above that it derates linearly: 156 A at 55 °C, 151 A at 60 °C, 147 A at 65 °C, and 142 A at 70 °C. The minimum operating temperature is -25 °C, which covers most unheated warehouses in temperate climates. Maximum power loss is 33 W at full load — factor that into the enclosure thermal budget if you're stacking several breakers side by side.

Frequently asked questions

What is the depth of 3VA1216-5EF32-0AD0?

70 mm (2.76 in), which is the dimension that governs clearance behind the panel door or gland-plate space.

Will 3VA1216-5EF32-0AD0 drop into a panel specified around 3VA1110-5ED36-0AC0?

Both breakers share the same SENTRON 3VA frame dimensions (105 mm wide, 158 mm tall, 70 mm deep), so the physical mounting and busbar positions are identical. The difference is the TM240 release and 160 A rating versus the lower-amp sibling — the load conductors and upstream protection must be sized for 160 A.

MPN
3VA1216-5EF32-0AD0