Skip to main content
Siemens 3VA1216-5EF32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-5EF32-0AJ0 SENTRON MCCB, 160 A, 3-Pole, TM24

MPN3VA1216-5EF32-0AJ0

Siemens SENTRON 3VA1216-5EF32-0AJ0, molded case circuit breaker, 3-pole, 160 A, TM240 thermal-magnetic trip, 187 kA at 240 V, 70 x 105 x 158 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1216-5EF32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA1216-5EF32-0AJ0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C155.6 A
Current at 60 °C151.2 A
Current at 65 °C146.8 A
Current at 70 °C142.4 A
Switching capacity classS
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1216-5EF32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1216-5EF32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-5EF32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1216-5EF32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-5EF32-0AJ0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

Line protection MCCB, 160 A frame, TM240 trip

The Siemens SENTRON 3VA1216-5EF32-0AJ0 is a 3-pole molded case circuit breaker rated for line protection, carrying a continuous current Iu of 160 A and a rated insulation voltage Ui of 800 V. Breaking capacity reaches 187 kA at 240 V and 121 kA at 415 V, with derated values of 36 kA at 440 V and 17 kA at 690 V.

The breaker holds its full 160 A rating from 40 °C through 50 °C ambient. Above that it derates linearly: 155.6 A at 55 °C, 151.2 A at 60 °C, 146.8 A at 65 °C, and 142.4 A at 70 °C. Dimensions are 70 mm deep by 105 mm wide by 158 mm high, with IP40 protection on the front face.

Frequently asked questions

What is the breaking capacity of 3VA1216-5EF32-0AJ0 at 415 V?

121 kA at 415 V, with derated values of 36 kA at 440 V and 17 kA at 690 V.

Where can I buy 3VA1216-5EF32-0AJ0?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What trip unit does 3VA1216-5EF32-0AJ0 use?

A TM240 thermal-magnetic overcurrent release with fixed settings — no voltage trigger, undervoltage release, or ground-fault monitoring.

MPN
3VA1216-5EF32-0AJ0