Skip to main content
Siemens 3VA1216-5EF32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-5EF32-0AF0 SENTRON MCCB, 160 A, 3-Pole, 187

MPN3VA1216-5EF32-0AF0

Siemens SENTRON 3VA1216-5EF32-0AF0, molded case circuit breaker, 3-pole, line protection, rated 160 A, interrupting 187 kA at 240 V AC, TM240 thermal-magnetic release, 1 aux + 1 trip alarm HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1216-5EF32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1216-5EF32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C155.6 A
Current at 60 °C151.2 A
Current at 65 °C146.8 A
Current at 70 °C142.4 A
Switching capacity classS
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1216-5EF32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1216-5EF32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-5EF32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1216-5EF32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-5EF32-0AF0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

Its 160 A rated continuous current (Iu) holds flat from 40 °C through 50 °C, then derates to 155.6 A at 55 °C, 151.2 A at 60 °C, 146.8 A at 65 °C, and 142.4 A at 70 °C — so in a warm enclosure you lose about 11 % of capacity by 70 °C. The interrupting ratings tell the real story: 187 kA at 240 V, 121 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V. The TM240 thermal-magnetic release is fixed-trip, not electronic, so no adjustment dials; you spec it for the cable and load and it stays.

Frequently asked questions

Where can I buy the 3VA1216-5EF32-0AF0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and the desk will come back with a firm number.

What is the closest functional alternative — will the 3VA1112-5EF32-0CA0 drop in without rewiring?

The 3VA1112-5EF32-0CA0 is a lower-current sibling in the same SENTRON 3VA frame family, but it is not a direct mechanical swap: the 3VA1216 carries a 160 A TM240 release while the 3VA1112 uses a different trip rating. The footprint (105 mm width, same mounting centers) is shared, so a panel cutout fits either, but the cable sizing and protection coordination change — you re-spec the feeder, not just swap the breaker.

What compliance documentation does Siemens provide for this MCCB?

Siemens provides RoHS, REACH, and CE declarations for the SENTRON 3VA series. The part carries a UL and IEC certification path as standard for industrial MCCBs — the specific UL file number and IEC test reports are included in the manufacturer's documentation package upon request.

MPN
3VA1216-5EF32-0AF0